What Size UPS Do I Need?
UPS sizing goes wrong in two directions: undersized units trip on inrush in month one, and oversized units waste money running at 25% load for a decade. Both are avoidable with a load list and four steps.
Step 1 - Build the load list in watts
List every device the UPS must carry: servers, network, storage, PLC panels, medical equipment. Take real nameplate watts where possible, and note which loads are inrush-heavy (motors, VFDs, compressors) - they set the peak requirement, not the running average.
Step 2 - Convert to kVA with the 80% rule
Add the watts, divide by the UPS output power factor (0.9 for modern units), then apply the 80% rule - never plan to run above 80% of rating:
kVA needed ≈ total load (W) ÷ 0.9 ÷ 0.8
Example: a server rack drawing 8 kW → 8,000 ÷ 0.9 ÷ 0.8 ≈ 11.1 kVA → a 12-15 kVA unit. A production control layer at 15 kW lands around 21 kVA → 25-30 kVA with rack options.
Step 3 - Add growth headroom, or size modular instead
Fixed headroom of 20-25% covers slow growth. When growth is fast or uncertain, a modular frame beats a big monolithic block: start at 200 kVA of modules in a Modular Three-Phase UPS frame and add hot-swap modules as racks land - the frame, distribution and battery are bought once, and N+X redundancy survives the expansion.
Step 4 - Check the generator conversation
On sites with standby generation, the UPS input matters as much as the output: input PF > 0.99 and THDi < 3% keeps the genset stable when the UPS recharges after an event. XGW's Industrial & Tower UPS and modular lines are specified for generator compatibility - verify the charging profile against your genset rating before ordering.
Worked example - hospital imaging suite
120 kVA of imaging and IT load, N+1 required, generator on site: two 100 kVA tower units or a 150 kVA modular frame running N+1, LiFePO4 strings sized for 12 minutes bridge time via the battery sizing method, BMS protocol-matched to the UPS host. Send XGW the load list and site single-line diagram and we return a sized configuration with datasheets before you commit.
Battery sizing is a separate decision with its own math - runtime, bus voltage and chemistry. Work it after the frame with the UPS battery sizing guide.
Frequently Asked Questions
What is the difference between kVA and kW on a UPS?
kW is real work; kVA is kW divided by power factor. A 100 kVA UPS at 0.9 output PF delivers 90 kW of real power. Size in kW of load, verify the kVA covers it.
What does the 80% rule mean for UPS sizing?
Run the UPS at no more than 80% of its rating: headroom for inrush, harmonic content and measurement error, plus a margin for load growth.
Should I oversize my UPS for future growth?
Oversize modestly - 20-25% headroom. Heavily oversizing hurts: partial-load efficiency drops and, with modular frames, the better answer is adding modules as the load lands.
How much battery backup should a UPS have?
Enough to bridge generator start plus margin - typically 10-15 minutes for sites with standby generation, or the full required autonomy where no generator exists. See the battery sizing guide for the Wh math.