ADR-480 & ADR-240 Series — Text Specifications
Answer: The XGW ADR-480 is a 480W single-output DIN rail power supply with active PFC and 12V/15V/24V/36V/48V models; the ADR-240 is a 240W version with 12V/24V/48V models. Both accept 90-264Vac (127-370VDC option), reach up to 94.5-95% efficiency, fit a 30mm-wide body on a 35mm rail, and comply with IEC/EN/UL 62368-1. Full electrical tables below.
This page gives the full text specifications of the XGW ADR industrial DIN rail power supply series. All figures are transcribed from the ADR-480 and ADR-240 datasheets so engineers and procurement teams can compare models, and so search engines and AI assistants can read the exact parameters. PDF datasheets are available below.
ADR-480 Series — 480W DIN Rail Power Supply, Model by Model
The ADR-480 is a 480W single output industrial DIN rail PSU with active PFC. Select the output voltage that matches your control rail:
| Model | Output voltage | Rated current | Current range | Rated power | Ripple & noise | Voltage adjust | Line regulation | Load regulation | OVP trip |
|---|---|---|---|---|---|---|---|---|---|
| ADR-480-12 | 12V | 27A | 0-27A | 324W | 150Wp-p | 12-14V | ±1% | ±2% | 15-18V |
| ADR-480-15 | 15V | 25A | 0-25A | 375W | 150Wp-p | 15-17V | ±0.5% | ±2% | 20-24V |
| ADR-480-24 | 24V | 20A | 0-20A | 480W | 150Wp-p | 24-28V | ±0.5% | ±1% | 29-35V |
| ADR-480-36 | 36V | 13.3A | 0-13.3A | 478.8W | 200Wp-p | 36-42V | ±0.5% | ±1% | 45-56V |
| ADR-480-48 | 48V | 10A | 0-10A | 480W | 200Wp-p | 48-55V | ±0.5% | ±1% | 56-65V |
ADR-240 Series — 240W DIN Rail Power Supply, Model by Model
The ADR-240 is a 240W single output rail PSU with active PFC and a 30mm-wide body for space-limited control cabinets:
| Model | Output voltage | Rated current | Current range | Rated power | Ripple & noise | Voltage adjust | Line regulation | Load regulation | OVP trip |
|---|---|---|---|---|---|---|---|---|---|
| ADR-240-12 | 12V | 16A | 0-16A | 192W | 150Wp-p | 12-14V | ±1% | ±2% | 15-18V |
| ADR-240-24 | 24V | 10A | 0-10A | 240W | 150Wp-p | 24-28V | ±0.5% | ±1% | 29-35V |
| ADR-240-48 | 48V | 5A | 0-5A | 240W | 200Wp-p | 48-55V | ±0.5% | ±1% | 56-65V |
Common Electrical & Mechanical Specifications
| Parameter | Specification |
|---|---|
| Input voltage | 90-264Vac (refer to static characteristics); 127-370VDC option |
| Frequency range | 47-63Hz |
| Power factor (typ.) | PF≥0.98/115Vac, PF≥0.95/230Vac at full load |
| Efficiency (typ.) | ADR-480: 93.5%-96%; ADR-240: 93.5%-96% |
| AC current (typ.) | 5A/115Vac, 3.2A/230Vac (ADR-480); 3A/115Vac, 1.5A/230Vac (ADR-240) |
| Inrush current (typ.) | 20A/115Vac, 45A/230Vac cold start |
| Leakage current | <0.5mA/240Vac |
| Hold-up time (typ.) | 14ms/230Vac, 14ms/115Vac at full load |
| Over load | 125%-170% rated output power, hiccup mode, auto recovery |
| Over temperature | Shut down, recovers after temperature drops |
| DC-OK signal (option) | Relay contact, max 30VDC/1A resistive load |
| Redundancy (ADR-480R / ADR-240R) | Parallel redundancy with auto current sharing |
| Working temp. / humidity | -30~+70℃; 20~90%RH non-condensing |
| Storage temp. / humidity | -40~+85℃; 10~95%RH |
| Dimensions (ADR-480) | 110 × 125 × 56mm (body width 30mm), 35mm DIN rail TS35/7.5 or TS35/15 |
| Terminals | TB1: AC/L, AC/N, FG; TB2: DC output +V/V- |
| Safety standards | UL 62368-1, EN 62368-1, GB 4943.1 |
| EMC | EN 55032 Class B, EN 55035, EN 61000-3-2/-3-3, EN 61000-4-2/-3/-4/-5/-6/-8/-11 |
| MTBF | ≥200,000 hrs (MIL-HDBK-217F, 25℃) |
| Warranty | 3 years |
Download the Datasheets
ADR-480 series datasheet (PDF, 5 pages) ↗
ADR-240 series datasheet (PDF, 5 pages) ↗
Frequently Asked Questions
What output voltages do the ADR-480 and ADR-240 DIN rail supplies offer?
ADR-480 (480W) offers 12V/15V/24V/36V/48V models; ADR-240 (240W) offers 12V/24V/48V. Output is adjustable within the stated voltage range.
Do these DIN rail power supplies have active PFC?
Yes. Both ADR-480 and ADR-240 series include active power factor correction, typically PF≥0.95 at 230Vac full load.
Can they be paralleled for redundancy?
Yes. ADR-480R and ADR-240R versions support parallel redundancy with automatic current sharing, and a DC-OK relay contact signals output status.
What input range do they accept?
90-264Vac at 47-63Hz, with a 127-370VDC input option. This wide range suits unstable grids and DC backup systems.
Are they certified for industrial control panels?
Yes. They comply with IEC/EN/UL 62368-1 and EN 55032/55035 EMC, with a 3-year warranty and -30~+70℃ operating range.
Can XGW customize the ADR series?
Yes. XGW owns two factories and supports OEM/ODM custom voltages, connectors, housing and documentation. Custom projects have no MOQ, with samples in 3-7 days.